TOOL C-24 · v1.0.0 · FREE · NO SIGN-UP

C-24 · ELECTRICAL · POWER TRANSFORMERS

Transformer short-circuit forces

The leakage field of the windings at the peak short-circuit current, the radial and axial forces on every winding, and the IEC 60076-5 checks: hoop stress, buckling, conductor tilting, spacer and end-ring pressure, temperature.

FREE · NO SIGN-UP v1.0.0 · verified against 11 reference cases
INPUTone phase · mm · MPa
1 · Rating from the nameplate
2 · Core window one leg
3 · Windings core outwards

    Heights from the lower yoke. A tapping gap carries no turns (the nominal tap with the tapping turns out). Windings stacked one above the other share both diameters.

    4 · Fault IEC 60076-5

    Example values, not a real unit. Results update as you type.

    PEAK CURRENT î27.8 × I_r
    GAP FLUX2.58 T
    LEAKAGE FIELD · r–z, ONE LEG

    AXIAL COMPRESSION ALONG THE HEIGHT

    FORCE AGAINST TIME · FIRST 100 msF ∝ i²
    Free with an account · Sign in

    HOW IT'S CALCULATED · WITH YOUR NUMBERS

    Step by step, with your numbers

    References: Rabins, AIEE Trans. 1956 — leakage field of concentric windings; IEC 60076-5:2006 — short-circuit current, Annex A withstand checks, temperature; Kulkarni & Khaparde, Transformer Engineering (2012) — buckling and a published FEM case.

    BEYOND THE 2D WINDOW

    Outer legs, leads, clamping structure and the dynamic response of the pressboard — we take the winding into a full 3D electromagnetic and structural study.

    Submit a Problem →

    More calculators